VR SOLAR 1118
Tel: (51-1) 717-8340
info@lgtsolar.com
Beneficios
Especificaciones
Documentos
High density pasted plates for high cycle life
Nano-Carbon enhanced active material to maximize cycle performance and PSoC operation
Low calcium Lead/Tin alloy plates for efficient gas recombination for long life in both cycling and float applications
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance
Multicell design for economy of installation and maintenance
Front Access threaded copper alloy inserts for reduced maintenance and increased safety
Terminal versatility - ease of diagnostic readings with C&D Ohmin Ring
Reduced headspace driving higher energy density, in cabinet or rack applications
Can be used in any orientation. Upright, side, or end mounting recommended
High-strength, leak-free polymer container allows for non-restricted shipping;
Water: non-hazardous per IMDG Amendment 27
Surface: non-hazardous per DOT-CFR title 49,
171-189 Air: IATA/ICAO, provision A67
UL-recognized component
Battery hardware and removable carrying handles included
Meets IEC 61421 for PV applications
Multitier racks and cabinets available
6
Cells Per Unit
Nominal Voltage Per Unit
12
Weight
159 lbs (72.0 kg)
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Operating Temperature Range
Optimal Operating
Temperature Range
+74°F (23°C) to +80°F (27°C)
Recommended Maximum Charging
Current Limit
30 amperes per 100Ah @ C20 (62.4A)
Float Charging Voltage
13.62 to 13.8 VDC/unit Average at 77°F (25°C)
Equalization and
Cycle Service
Charging Voltage
14.4 to 14.8 VDC/unit Average at 77°F (25°C)
Maximum AC Ripple
0.5% RMS or 1.5% P-P of float charge voltage recommended for best results
Maximum voltage allowed = 4% P-P
Maximum current allowed = C20 RMS (20 Amps)
Self Discharge
Up to 6 months at 77°F (25°C) and then a freshening charge is required.
Batteries stored at temperatures at greater than +77°F (25°C) will require recharge
sooner than batteries stored at temperatures less than 77°F (25°C).
See C&D bulletin 41-7272, Self Discharge and Inventory Control for details
Temperature
Compensation
Factor (Charging)
+3 mv/F per cell when operating, below 77°F (+25°C)
-3 mv/F per cell when operating, above 77°F (+25°C)
Terminal
Threaded copper alloy insert terminal to accept 5/16´´ - 18 bolt
Terminal Hardware
Initial Torque
160 in.-lbs (18 N-m)
The VR Solar Front Access, with its grid alloy and DCS Technology, coupled with an advanced Nano-Carbon enhanced negative electrode provides time proven results and unmatched, industry leading cycle life even in partial state of charge (PSoC) operation. This VRLA/AGM baterry is designed to be easy to install and maintain, and offers long life and exceptional performance.