 High density pasted plates for high cycle life

Nano-Carbon enhanced active material to maximize cycle performance and PSoC operation

Low calcium Lead/Tin alloy plates for efficient gas recombination for long life in both cycling and float applications

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance

Multicell design for economy of installation and maintenance

Front Access threaded copper alloy inserts for reduced maintenance and increased safety

Terminal versatility - ease of diagnostic readings with C&D Ohmin Ring

Reduced headspace driving higher energy density, in cabinet or rack applications

Can be used in any orientation. Upright, side, or end mounting recommended

High-strength, leak-free polymer container allows for non-restricted shipping;

Water: non-hazardous per IMDG Amendment 27

Surface: non-hazardous per DOT-CFR title 49,

171-189 Air: IATA/ICAO, provision A67

UL-recognized component

Battery hardware and removable carrying handles included

Meets IEC 61421 for PV applications

Multitier racks and cabinets available

6

Cells Per Unit

Nominal Voltage Per Unit

12

Weight

159 lbs (72.0 kg)

Discharge: -40°F (-40°C) to +160°F (71°C)

Charge: -10°F (-23°C) to +140°F (60°C)

Operating Temperature Range

Optimal Operating

Temperature Range

+74°F (23°C) to +80°F (27°C)

Recommended Maximum Charging

Current Limit

30 amperes per 100Ah @ C20 (62.4A)

Float Charging Voltage

13.62 to 13.8 VDC/unit Average at 77°F (25°C)

Equalization and

Cycle Service

Charging Voltage

 

14.4 to 14.8 VDC/unit Average at 77°F (25°C)

Maximum AC Ripple

0.5% RMS or 1.5% P-P of float charge voltage recommended for best results

Maximum voltage allowed = 4% P-P

Maximum current allowed = C20 RMS (20 Amps)

 

Self Discharge

Up to 6 months at 77°F (25°C) and then a freshening charge is required.

Batteries stored at temperatures at greater than +77°F (25°C) will require recharge

sooner than batteries stored at temperatures less than 77°F (25°C).

See C&D bulletin 41-7272, Self Discharge and Inventory Control for details

Temperature

Compensation

Factor (Charging)

+3 mv/F per cell when operating, below 77°F (+25°C)

-3 mv/F per cell when operating, above 77°F (+25°C)

 

Terminal

Threaded copper alloy insert terminal to accept 5/16´´ - 18 bolt

Terminal Hardware

Initial Torque

160 in.-lbs (18 N-m)

The VR Solar Front  Access, with its grid alloy and DCS Technology, coupled with an advanced Nano-Carbon enhanced negative electrode provides time proven results and unmatched, industry leading cycle life even in partial state of charge (PSoC) operation. This VRLA/AGM baterry is designed to be easy to install and maintain, and offers long life and exceptional performance.